RV-K 0.6/1kV
Use
industrial low voltage installations and connections;
✔ power supply or fixed station links;
✔ laying in cable trays on shelves or other supports and on building risers
in gutters or buried with mechanical protection.
Description
1- Flexible class 5 annealed copper core
NFC 32-013 / IEC 60228 standards
2- Insulation : PR / XLPE
Standards NM 06-3-006 / IEC 60502-1 / NFC32-321
3- PVC assembly coating
4. Sheath: flexible black or gray PVC
Standards NM 06-3-006 / NFC 32-32
Technical specifications
Code HANFORD | Section | Approx. outer diameter | Approx. weight | Admissible current | Voltage drop Cosø=0.8 |
Outdoors 30°C | In ground 20°C |
mm2 | mm | Kg/Km | A | V/A/Km |
1 Copper conductor | Three-phase |
RVK1.5 | 1 x 1.5 | 5.6 | 41 | 24 | 31 | 26 |
RVK2.5 | 1 x 2.5 | 6.0 | 55 | 33 | 41 | 15 |
RVK4 | 1 x 4 | 6.5 | 75 | 45 | 53 | 10.2 |
RVK6 | 1 x 6 | 7.3 | 100 | 58 | 66 | 6.83 |
RVK10 | 1 x 10 | 8.0 | 140 | 80 | 87 | 4.06 |
RVK16+ | 1 x 16 | 8.9 | 200 | 107 | 113 | 2.55 |
RVK25+ | 1 x 25 | 11.4 | 300 | 138 | 144 | 1.60 |
RVK35+ | 1 x 35 | 12.7 | 400 | 169 | 174 | 1.16 |
RVK50+ | 1 x 50 | 14.5 | 535 | 207 | 206 | 0.86 |
RVK70+ | 1 x 70 | 16.7 | 740 | 268 | 254 | 0.59 |
RVK95+ | 1 x 95 | 18.8 | 950 | 328 | 301 | 0.43 |
RVK120+ | 1 x 120 | 20.8 | 1200 | 382 | 343 | 0.34 |
RVK150+ | 1 x 150 | 23.5 | 1500 | 441 | 387 | 0.27 |
RVK185+ | 1 x 185 | 25.5 | 1900 | 506 | 434 | 0.22 |
RVK240 | 1 x 240 | 28.8 | 2350 | 599 | 501 | 0.17 |
RVK300 | 1 x 300 | 31.5 | 3000 | 693 | 565 | 0.13 |