H07 V-U/ H07 V-R
Use
- Equipment of lighting circuits and sockets in premises for residential use, offices, etc.
- Fixed installations in exposed or recessed ducts
Description
1- Core
Solid round copper for S ≤ 4mm2
Wired round copper for S ≥ 6mm2
2- Insulation
Colored PVC: R: red, B: blue, N: black,
G: green/yellow, B: white, G: grey, Y: yellow,
Special points
› Nominal voltage Uo/U: 450/750 V
› Test voltage: 2500 V ≈
Technical specifications
Code HANFORD | Section | Max. resistance in C.C at 20°C
| Outer diameter approx.
| Approx. weight
| Admissible current
| Voltage drop
|
Nber of conductors | Single | 3-phase |
2 | 3 | 4 |
mm2 | Ω/KM | mm | Kg/Km | A | V/A/Km |
HVU1.5+ | 1x1.5 | 12.10 | 2.7 | 19 | 18 | 15.5 | 14 | 23.0 | 20.0 |
HVU2.5+ | 1x2.5 | 7.41 | 3.3 | 30 | 24 | 21.0 | 19 | 14.0 | 12.0 |
HVU 4 | 1x4 | 4.61 | 3.8 | 45 | 32 | 28.0 | 25 | 8.90 | 7.7 |
HVR6 + | 1x6 | 308 | 4.5 | 63 | 41 | 36 | 32 | 6.00 | 5.20 |
HVR10 + | 1x10 | 1.83 | 5.7 | 110 | 57 | 50 | 44 | 3.60 | 3.10 |
HVR16 + | 1x16 | 1.15 | 6.7 | 154 | 76 | 68 | 59 | 2.30 | 2.00 |
HVR25 + | 1x25 | 0.727 | 8.2 | 260 | 96 | 89 | 77 | 1.50 | 1.30 |
HVR35 + | 1x35 | 0.524 | 9.2 | 355 | 119 | 110 | 95 | 1.10 | 0.95 |
HVR50 | 1x50 | 0.387 | 10.7 | 480 | 144 | 134 | 115 | 0.84 | 0.72 |
HVR70 | 1x70 | 0.268 | 12.4 | 670 | 184 | 171 | 147 | 0.60 | 0.52 |
HVR95 | 1x95 | 0.193 | 14.5 | 920 | 223 | 207 | 178 | 0.46 | 0.40 |
HVR120 | 1x120 | 0.153 | 16.0 | 1170 | 259 | 239 | 207 | 0.38 | 0.33 |
HVR150 | 1x150 | 0.124 | 17.7 | 1430 | 299 | 275 | 239 | 0.33 | 0.29 |
HVR185 | 1x185 | 0.0991 | 19.6 | 1790 | 341 | 314 | 273 | 0.28 | 0.24 |
HVR240 | 1x240 | 0.0754 | 23.0 | 2360 | 403 | 370 | 322 | 0.24 | 0.21 |
HVR300 | 1x300 | 0.0601 | 25.5 | 2880 | 460 | 424 | 369 | 0.21 | 0.18 |